CRITICALPhishing
Global

Danfoss AK-SM 8xxA Series

·Source: CISA Advisories

Updated:

Executive Summary

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code with webserver privileges. The following versions of Danfoss AK-SM 8xxA Series are affected: AK-SM8xxA <=5.4.

Analysis

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code with webserver privileges. The following versions of Danfoss AK-SM 8xxA Series are affected: AK-SM8xxA CVSS Vendor Equipment v3 9.8 Danfoss AK-SM8xxA 1 Vulnerability Stack-based Buffer Overflow Background Critical Infrastructure Sectors: Commercial Facilities Countries/Areas Deployed: Worldwide Company Headquarters Location: Denmark Vulnerabilities CVE-2026-129713 A stack-based buffer overflow in an unauthenticated CGI handler of the Danfoss AK-SM 8xxA Series controller allows remote attackers to send specially crafted HTTP/S POST requests, leading to memory corruption, webserver restart and hypothetically potential arbitrary code execution with webserver privileges. Authentication is not required to exploit this vulnerability. Read More 1 Affected Product Danfoss AK-SM8xxA Product Status: known_affected Remediations Mitigation This vulnerability will be addressed in an upcoming Danfoss AK-SM 800A Series software release (version 5.5.x). Mitigation In addition, Danfoss will remove the ability for users to disable Strict Mode in future software releases. Additional Metrics Relevant CWE: CWE-121 Stack-based Buffer Overflow CVSS Version Base Score Base Severity Vector String 3.1 9.8 CRITICAL CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H 4.0 9.3 CRITICAL CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N View CVE Details Acknowledgments Carlo Meijer of Midnight Blue reported CVE-2026-129713 to CISA. Recommended Practices CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet . Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics . Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies . CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets . Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies . Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents. CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks. No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. Revision History Initial Release Date: 2026-11-24 Date Revision Summary 2026-11-24 1 Initial Publication Legal Notice and Terms of Use

Indicators of Compromise (8)

CVE (1)
CVE-2026-129713
URL (4)
https://cwe.mitre.org/data/definitions/121.html
https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
https://www.cve.org/CVERecord?id=CVE-2026-129713
Domain (3)
cwe.mitre.org
www.first.org
Source Attribution

Originally published by CISA Advisories on Nov 24, 2026.